excodex

The book Chapter 7

Question and answerEXC-QA-293

How do North American T-codes such as T2A or T3C differ from IEC T-classes?

excodex editorial teamCertification and testing

Abstract

The NEC Division system adds eight codes between the IEC classes: T2A 280, T2B 260, T2C 230, T2D 215, T3A 180, T3B 165, T3C 160 and T4A 120 °C. T1 to T6 keep the IEC limits. The finer steps allow hotter equipment where a gas AIT sits just above a class limit.

They use the same principle and the same six main limits, but the North American Class and Division system adds eight intermediate codes. T2A to T2D (280 to 215 °C), T3A to T3C (180 to 160 °C) and T4A (120 °C) give finer steps between the IEC classes. A T-code is acceptable when its temperature does not exceed the autoignition temperature (AIT) of the gas, so the extra steps let somewhat hotter equipment be used for gases whose AIT lies just above a class limit.

Short answer

  • IEC (and NEC Article 505 for Zones): six classes, T1 450, T2 300, T3 200, T4 135, T5 100 and T6 85 °C.
  • NEC Article 500 (Divisions), Table 500.8(C): the same six plus T2A 280, T2B 260, T2C 230, T2D 215, T3A 180, T3B 165, T3C 160 and T4A 120 °C.
  • Rule in both systems: the marked temperature must not exceed the AIT of the gas or vapour.
  • In IEC terms a T2A to T2D device is only T2, a T3A to T3C device is T3 and a T4A device is T4.
  • US temperature markings are based on operation in a 40 °C ambient (29 CFR 1910.307); equipment for hotter ambients is marked with its ambient range.
  • Under the 2017 NEC, non-heat-producing equipment (junction boxes, conduit, fittings) and heat-producing equipment that stays at or below 100 °C need no temperature marking at all.

The two tables side by side

Maximum surface temperatureIEC classNEC Article 500 code
450 °CT1T1
300 °CT2T2
280 °C(none)T2A
260 °C(none)T2B
230 °C(none)T2C
215 °C(none)T2D
200 °CT3T3
180 °C(none)T3A
165 °C(none)T3B
160 °C(none)T3C
135 °CT4T4
120 °C(none)T4A
100 °CT5T5
85 °CT6T6

Values from the 2017 edition of NFPA 70, the National Electrical Code (NEC), Tables 500.8(C) and 505.9(D)(1); the 2026 edition is now current, so check the table and section numbers in the edition adopted locally. Article 505, which applies the IEC-style Zone system in the United States, uses only T1 to T6, but it allows equipment identified for Divisions, and marked with Division codes, where 505.20 permits it.

Vertical temperature scale with the six IEC classes on the left and the fourteen NEC codes on the right; the eight intermediate NEC codes T2A to T4A sit between the IEC steps, and a dashed line for hexane at 225 °C passes between T2C and T2D
The NEC adds eight intermediate codes to the six IEC classes. For hexane (AIT 225 °C), T2D is the hottest acceptable NEC code, while the IEC scale has nothing between T2 and T3, so T3 is needed.

Why the intermediate codes matter

The selection rule is the same in both systems: NEC 500.8(D)(1) states that the temperature marking must not exceed the AIT of the specific gas or vapour, and IEC 60079-0 states that the maximum surface temperature must not exceed the lowest ignition temperature. The difference is only resolution.

The IEC scale jumps from 300 to 200 °C. A gas with an AIT of 225 °C therefore needs T3 equipment, even though a device that never exceeds 215 °C would be safe by the same rule. The NEC scale can express that: a luminaire marked T2D (215 °C) is acceptable for hexane (AIT 225 °C in the excodex library), and one marked T2C (230 °C) is not. For lighting, heaters and motors, where every degree costs power, the finer codes can make a real difference.

Converting between the systems

NEC code to IEC requirement. Round down to the main number: T2A to T2D are hotter than 200 °C and only satisfy an IEC T2 requirement; T3A to T3C satisfy T3; T4A satisfies T4. A T3C device (160 °C) does not satisfy T4 (135 °C).

IEC class to NEC requirement. Each IEC class has an NEC code with the same limit, so IEC T3 equipment satisfies a T3 requirement and every hotter code (T2D, T2C and so on up to T1), but not T3A, T3B or T3C.

Gas data to code. Use the AIT, not the IEC class of the gas. A North American area drawing may say "Class I, Division 1, Group D, T2D" because the actual AIT allows it, while the same substance in an IEC drawing is "IIA T3".

Example: A US plant handles a solvent with an AIT of 235 °C. The area is marked T2C (230 °C). A listed explosionproof luminaire marked T2B (260 °C) is not acceptable; one marked T2C, T2D or T3 is. If the plant later buys IECEx-certified equipment for a Zone area, the same solvent needs IEC T3, because a T2C rating does not exist in IEC.

Common mistakes

  • Reading T2A as cooler than T2D. Within a group the letters go from hotter to cooler: T2A 280 °C, T2D 215 °C.
  • Treating T3C as T4. 160 °C is still above the T4 limit of 135 °C.
  • Comparing the area code instead of the AIT. A T2D area requirement is met by T2D, T3, T4 and cooler equipment, not by T2C.
  • Forgetting the ambient reference. Both systems mark the class for a stated ambient range. The 2017 NEC needs no ambient marking for -25 to +40 °C (Article 500) or -20 to +40 °C (Article 505); other ranges are marked with Ta or Tamb.
  • Assuming certificates are interchangeable. Onshore US and Canada do not accept IECEx certificates directly; the temperature marking is only one of the differences.

Related on excodex

Standards and further reading

  • NFPA 70, National Electrical Code, Articles 500 and 505 (temperature marking tables; 2017 edition checked, 2026 edition current; check the edition adopted locally).
  • IEC 60079-0, general requirements (temperature classes T1 to T6).
  • ISO/IEC 80079-20-1, AIT data and temperature class of gases and vapours.
  • NFPA 70 (2017), public copy: archive.org
  • 29 CFR 1910.307, hazardous (classified) locations, marking at 40 °C ambient and temperature not above the ignition temperature: ecfr.gov
  • IS/IEC 60079-20-1:2010 public copy (temperature class table for gases): law.resource.org

This article is general technical information prepared by the excodex editorial team. It does not replace the applicable standards, the equipment certificates and instructions, national regulations or the assessment of a competent person.

excodex

Tools

Ex check Gas library exai Occupational safety My files

Community

excodex

Join free

Language

Sign in

Not a member yet? Join free

Improve the translation