excodex

The book Chapter 3

Question and answerEXC-QA-119

Why does a vented dust collector still need isolation on the inlet duct?

excodex editorial teamDust explosions

Abstract

Because a vent only limits the pressure inside the collector. The same explosion drives flame and pressure back through the inlet duct to the machines and rooms it serves. An isolation device in the inlet duct closes that path.

Because a vent protects only the collector housing, not the duct that feeds it. When dust explodes inside a vented collector, the vent keeps the pressure in the housing below its strength, but the same explosion pushes flame and pressure back through the inlet duct towards the machines, pickup points and rooms it serves. An isolation device in the inlet duct closes that path; without one, an explosion in the collector can travel back into the building.

Short answer

  • A vent opens at a set pressure and relieves the explosion to the outside. It does nothing to the other openings of the collector, and the inlet duct is usually the most direct path back into the plant.
  • During the explosion the pressure in the collector rises above the pressure in the duct, so the normal airflow reverses and burning dust is driven back towards the source.
  • Flame travelling through a duct speeds up and can enter connected equipment or a room as a jet, raising and igniting settled dust. The resulting secondary explosion can be far worse than the first.
  • The usual answers are a passive isolation flap valve, an active fast-acting valve or a chemical barrier in the inlet duct, plus an isolated hopper outlet and interlocks that stop the fan and feed.
  • Whether a particular connection needs isolation is decided by the documented hazard assessment (the explosion protection document or dust hazard analysis), not by the vent design.

What happens in the inlet duct during a vented explosion

A collector's dirty side is normally a Zone 20 and contains the finest, most explosive fraction of the dust. When that cloud ignites, the explosion develops within a fraction of a second. The vent panel opens at its set pressure, but the pressure inside keeps rising to the reduced explosion pressure the vent was designed for. During that time the collector is the highest-pressure point in the system, and gas, flame and burning dust flow out of every opening: through the vent, and back through the inlet duct against the fan.

In the duct the flame front is pushed ahead of the expanding gas and accelerates. When it reaches the end of the duct it may find a machine housing, a cyclone, a hood at a workstation or an open pickup point in a room. EN 15089 notes that explosions are generally propagated by the flame rather than by the pressure wave, which is why isolation must detect, extinguish or block the flame front early.

Two investigated incidents show the consequence:

  • Huntington, Indiana, 2003 (aluminium dust). According to the US Chemical Safety Board (CSB), an explosion in a dust collector outside the building sent a pressure wave back through the ductwork into the plant. A fireball followed, lifting and igniting aluminium dust that had settled on rafters and equipment. One worker died and six others were injured, two of them by burns.
  • East Rutherford, New Jersey, 2012 (ink plant). The CSB reports that an explosion in a rooftop collector was contained by its suppression equipment, but the pressure reversed the airflow back towards the pre-mix room, where a flash fire burned seven workers. Protection of the collector alone did not protect the room.

What the codes and guidance expect

SourceWhat it says on connected equipment
HSE guidance HSG103 (UK)An explosion in one item of interconnected plant can spread to others; plant items should be separated by isolation methods such as rotary valves, chokes, suppression barriers or fast-acting valves, and conveying equipment should stop when a vent opens
EN 15089Isolation systems stop flame and pressure, or flame only, from passing through connecting pipes and ducts; they do not generally stop burning powder carried by the flow, which needs its own assessment
EN 16447Isolation flap valves for dust stop an explosion travelling against the normal flow direction, for vessels protected by venting, flameless venting, suppression or explosion-resistant design
NFPA 61 (2017), now consolidated in NFPA 660Isolation devices to prevent deflagration propagation between connected equipment where the assessment finds them necessary, as quoted by OSHA in a 2019 inspection letter to a corn milling plant

Choosing the inlet isolation

DeviceWorks byPoints to check
Isolation flap valvePassive: the pressure wave closes a flap held open by the normal airflow, and a latch keeps it closedOnly against the normal flow direction; minimum and maximum distance from the collector; dust build-up on the flap; dust type and Kst within the certificate
Fast-acting valveActive: a detector triggers a valve that closes in millisecondsDetector position versus closing time; regular function tests
Chemical barrierActive: a detector triggers a suppressant container that fills the ductStops the flame, not the pressure; distances and suppressant service

Example: A sanding line feeds an outdoor cartridge collector through a 400 mm duct that enters the building through the wall. The collector has vent panels. A certified flap valve is fitted in the outdoor section of the inlet duct within the distance range given in its instructions, a rotary valve certified for isolation sits under the hopper, and a burst indicator on the vent panel stops the fan, the rotary valve and the sanding line.

Common mistakes

  • Assuming the fan will hold the flame back. In an explosion the pressure in the collector exceeds what the fan can produce, and the flow reverses.
  • Installing a flap valve where the explosion can come from the other side, for example where a spark could ignite dust in the duct itself. A flap valve only isolates against the normal flow direction.
  • Fitting the valve too close to or too far from the collector, or in an orientation outside its certified installation conditions.
  • Forgetting the other openings: the hopper discharge and any clean-air duct returning to a workroom need their own answer.

Related on excodex

Standards and further reading

  • EN 15089:2009, explosion isolation systems: sample pages
  • EN 16447:2014, explosion isolation flap valves: standard summary
  • EN 14491:2012, dust explosion venting protective systems; NFPA 68, deflagration venting; NFPA 69, explosion prevention systems including isolation; NFPA 660, combustible dusts.
  • HSE, HSG103 Safe handling of combustible dusts (isolation of interconnected plant): hse.gov.uk (PDF)
  • OSHA inspection letter quoting NFPA 61 (2017) on isolation between connected equipment (2019): dol.gov (PDF)
  • US Chemical Safety Board, 2003 Huntington aluminium dust collector explosion: csb.gov
  • US Chemical Safety Board, 2012 East Rutherford flash fire: csb.gov

This article is general technical information prepared by the excodex editorial team. It does not replace the applicable standards, the equipment certificates and instructions, national regulations or the assessment of a competent person.

excodex

Tools

Ex check Gas library exai Occupational safety My files

Community

excodex

Join free

Language

Sign in

Not a member yet? Join free

Improve the translation